APC Smart-UPS. Uninterruptible Power Supply. 230 VAC User’s Manual. 990-7020C, Revision 7, 3/00. Initial Start-Up. To obtain warranty coverage, please fill out and return the warranty registration card now. Inspection Inspect the UPS upon receipt. Notify the carrier and dealer if there is damage.

Smart-UPS®X

Uninterruptible Power Supply

Low Voltage (100-127V)

SMX2000RMLV2U

SMX2200RMLV2U

SMX3000RMLV2U

SMX3000RMLV2UNC

SMX3000RMJ2U

High Voltage (200-240V)

SMX2200RMHV2U

SMX3000RMHV2U

SMX3000RMHV2UNC

Overview

About the UPS

Ups

The APC® by Schneider ElectricSmart-UPS®X is a high performance uninterruptible power supply (UPS). It provides protection for electronic equipment from utility power blackouts, brownouts, sags, and surges; small utility fluctuations and large disturbances. The UPS also provides battery backup power until utility power returns to safe levels or the batteries are fully discharged.

The Smart-UPSX has both high and low voltage models

Low Voltage (100-127V)

High Voltage (200-240V)

SMX2000RMLV2U

SMX2200RMHV2U

SMX2200RMLV2U

SMX3000RMHV2U

SMX3000RMLV2U

SMX3000RMHV2UNC

SMX3000RMLV2UNC

SMX3000RMJ2U

Safety

Read the Safety Guide included in the package before installing the UPS.

Inspect the UPS upon receipt. Notify the carrier and dealer if there is damage.

Recycle the packaging.

Heavy: The external battery packs (XLBPs) are heavy. Always install the XLBPs at the bottom of the rack. Install the UPS above the installed XLBPs.

Product Overview

Front panel

Battery

Smart Ups 2200 Rack Mount Manual

Battery connectorDisplay interfaceBezel

Smart-UPSX 2000/2200/3000 VA

1

Rear panel

SmartSlot

Controllable Outlet Group 3

UPS input

External battery pack connector

Ground screw

EPO connector

Controllable Outlet Group 1

Serial port

Controllable Outlet Group 2

USB port

2200 VA Low Voltage

2000 VA Low Voltage

su0494a

su0492a

3000 VA Low Voltage

2200/3000 VA High Voltage

su0495a

su0493a

Specifications

Operating Conditions

This unit is intended for indoor use only. Select a location sturdy enough to support the weight of the UPS and XLBP.

Do not operate the unit where there is excessive dust, or the temperature or humidity are outside the specified limits.

This unit has front and rear air vents. Allow adequate space for proper ventilation.

Environmental Specifications

Environmental factors impact battery life. High temperatures, poor utility power, and frequent, short duration discharges will shorten battery life.

For additional specifications, see the APC Web site at www.apc.com.

Operating 0° to 40° C (32° to 104° F)Temperature Storage -15°to 45° C (5° to 113° F)

charge UPS battery every six months

Maximum

Operating

3,000 m (10,000 ft)

Elevation

Storage

15,000 m (50,000 ft)

Humidity

0% to 95% relative humidity, non-condensing

Installation

UPS

For UPS installation information, see the Smart-UPSX2000-3000VAQuick-Startthat is included with the UPS. The guide is also available on the enclosed CD and the APC Web site at www.apc.com.

Network Management Card

For installation information, see the user manual provided with the Network Management Card (NMC). The user manual is also available on the APC Web site at www.apc.com.

External Battery Pack

For installation information, see the Smart-UPSX2000-3000VA External Battery Pack Installation guide that is included with the external battery pack. The guide is also available on the enclosed CD and the APC Web site at www.apc.com.

Operation

Connect Equipment to the UPS

Note: The UPS will charge to 90% capacity in the first three hours of normal operation.Do not expect full battery runtime capability during this initial charge period.

1.Connect equipment to the outlets on the rear panel of the UPS.

2.Connect the UPS to the building utility power. Connect the UPS to a two-pole,three-wire, grounded source only.

3.Press the ON/OFF button on the front panel of the UPS to power the unit and all connected equipment.

4.To use the UPS as a master on/off switch, turn on all the equipment that is connected to the UPS.

See “Switched Outlet Groups” on page 11 for information on how to use the Switched Outlet Groups.

su0475a

Basic Connections

Serial port: Connect to a computer to use power management software, use the serial cable included with the unit.

USB port: Connect to a computer to use power management software.

Note: Serial and USB communication can only be used individually, they cannot communicate at the same time.

External Battery Pack connector: Connect XLBPs to provide extended runtime during power outages. The UPS can support up to 10 external battery packs.

Ground Screw: The UPS features a ground screw for connecting the ground leads on transient voltage devices. Prior to connecting a ground lead, disconnect the UPS from utility power.

Display Interface

Overview

Online LED

UPS Output On/Off buttonOn Battery LED

Fault LED

Replace Battery LEDDisplay screen

Apc Smart Ups 1000 Manual

UPand DOWNbuttonsENTERbutton

ESCAPE button

Using the display interface

Use the UP andDOWN buttons to scroll through the main menu options. PressENTER to view thesub-menusunder each main menu option. PressESCAPE to exit asub-menuand return to a main menu.

Menu Overview

The Smart-UPShas Standard and Advanced menu screens. The Standard menu screens are the most commonly used screens. The Advanced menu screens are for more advanced users to configure additional features on the UPS.

Note: Actual menu screens may differ by model.

Main Menu

Overview

Standard

Advanced

Scrolling Screens

On Utility

x

(the UPS is operating on utility power)

Outlet Group Status

x

Input and Output voltage

x

Load meter

x

Battery charge and runtime

x

Warnings

x

Load and Battery graphs

x

Status

Operating Mode

x

x

Efficiency in % (Green mode only)

x

x

Input and output voltage

x

x

Load power (W) and VA

x

x

Main Menu

Overview

Standard Advanced

Configuration

Control

Test & Diagnostics

Statistics

Logs

Load (A)

x

Load meter (kWh)

x

Last transfer to battery power information

x

x

Battery charge and estimated run time

x

x

Battery voltage

x

Number of external battery packs

x

Internal battery temperature

x

Run time calibration test results

x

x

Self-testresults

x

x

Status of the switched outlet group(s): On,

x

Off, Sleep, Reboot, Turning On, Turning Off

Smart Slot information (if applicable)

x

Language

x

x

Local power quality

x

x

Standard or Advanced menus

x

x

Audible alarms

x

x

High and low transfer points

x

Low run time warning

x

Green mode (enable/disable)

x

Output voltage

x

x

Battery self-testinterval

x

x

Battery installation date

x

x

UPS firmware update (only available when

x

x

output is off)

UPS setup wizard

x

x

Reset to factory defaults

x

x

Switched outlet group(s) delays and settings

x

Smart Slot configuration (if applicable)

x

Switched outlet group(s): Turn on, turn off,

x

put to sleep, or reboot

UPS self-test.

x

x

Runtime calibration test.

x

x

Alarm and display test.

x

x

Statistics about transfers to battery power,

x

time on battery, and total operating time

Transfer log

x

Status log

x

Fault log

x

Main Menu

Overview

Standard

Advanced

About

General information about the UPS,

x

x

including: model numbers, output voltage

setting, serial number, manufacture date,

replacement battery cartridge information,

firmware versions, and suggested battery

replacement date.

SmartSlot card information (if applicable),

x

including IP address

PowerChute Business Edition information

x

(if applicable)

Configuration

UPS Settings

Start-upSettings

Use the display interface to configure these settings at initial start-up.The UPS will prompt for a response to each setting, if no response is given, the default setting will be used.

Note: The unit will not turn on until all of these settings are entered.

Function

Factory Default

Options

Description

Language

English

• English

The language for the display interface.

• French*

*Language options will vary by model.

• German*

• Spanish*

• Italian*

• Portuguese*

Output

Low Voltage: 120 V • 100

Voltage

• 110

• 120

Set the output voltage setting while the UPS is in

• 127

Standby mode.

High Voltage: 230 V • 200

208

Smart-ups Srt 2200 Manual

220

230

240

Apc Smart Ups 2200 Tower Manual

Input Power

Good

• Good

Select the quality of input utility power.

Quality

• Fair

• If Good is selected, the unit will go on battery

• Poor

power more often to provide the cleanest power

supply to the connected equipment.

• If Poor is selected, the UPS will tolerate more

fluctuations in power and will go on battery power

less often.

If unsure of the local power quality, select Good.

Menu Type

Standard

Standard or

The advanced menus include all parameters. The

Advanced

Standard menus display a limited set of menus and

options.

Date

UPS manufacture

mm-yyyy

Enter the current date.

date + 90 days

Apc Smart Ups 2200 Service Manual Pdf